AIChannel.InputLimitsFaultDetectLowerLimit Property
- Updated2023-02-21
- 1 minute(s) read
AIChannelInputLimitsFaultDetectLowerLimit Property
Specifies the level of the lower limit for input limits detection. An input sample outside the upper and lower bounds causes a fault. Note: Fault detection applies to both positive and negative inputs. For instance, if you specify a lower limit of 2 mA and an upper limit of 12 mA, NI-DAQmx detects a fault at 15 mA and -15 mA, but not at -6 mA because it is in the range of -12 mA to -2 mA.
Namespace: NationalInstruments.DAQmx
Assembly: NationalInstruments.DAQmx (in NationalInstruments.DAQmx.dll) Version: 20.7.40.49302
Syntax
public double InputLimitsFaultDetectLowerLimit { get; set; }
Public Property InputLimitsFaultDetectLowerLimit As Double Get Set
Property Value
Type: DoubleSpecifies the level of the lower limit for input limits detection. An input sample outside the upper and lower bounds causes a fault. Note: Fault detection applies to both positive and negative inputs. For instance, if you specify a lower limit of 2 mA and an upper limit of 12 mA, NI-DAQmx detects a fault at 15 mA and -15 mA, but not at -6 mA because it is in the range of -12 mA to -2 mA.
Exceptions
Exception | Condition |
---|---|
DaqException | The NI-DAQmx driver returned an error. |