Counter n Sample Clock Signal
- Updated2023-10-23
- 1 minute(s) read
Counter n Sample Clock Signal
Use the Counter n Sample Clock (CtrnSampleClock) signal to perform sample clocked acquisitions and generations.
You can specify an internal or external source for Counter n Sample Clock. You also can specify whether the measurement sample begins on the rising edge or falling edge of Counter n Sample Clock.
If the sbRIO controller receives a Counter n Sample Clock when the FIFO is full, it reports an overflow error to the host software.
Using an Internal Source
DI Sample Clock
DO Sample Clock
AI Sample Clock
AI Convert Clock
AO Sample Clock
DI Change Detection output
Several other internal signals can be routed to Counter n Sample Clock through internal routes. Refer to "Device Routing in MAX" in the NI-DAQmx Help or the LabVIEW Help for more information.
Using an External Source
Any PFI terminal
Analog Comparison Event
You can sample data on the rising or falling edge of Counter n Sample Clock.
Routing Counter n Sample Clock to an Output Terminal
You can route Counter n Sample Clock out to any PFI terminal. The PFI circuitry inverts the polarity of Counter n Sample Clock before driving the PFI terminal.