RM-26999 Safety Guidelines
- Updated2025-02-05
- 5 minute(s) read
RM-26999 Safety Guidelines
Icons
Protective Earth Ground

- The facility installation shall provide a means for connection to protective earth; and
- Qualified personnel shall install a protective earthing conductor from both protective earth terminals on the front panel of the RM-26999 to the protective conductor in the facility.
- L'installation du site doit fournir un moyen de connexion à la terre ; et
- Du personnel qualifié doit installer un conducteur de mise à la terre allant de la borne de mise à la terre située sur la face avant du RM-26999 jusqu'au câble de mise à la terre du site.
Safety Guidelines for Hazardous Voltages
A hazardous voltage is a voltage greater than 42.4 V peak voltage or 60 V DC in DRY LOCATIONS. If hazardous voltages are or will be connected to the device, take the following precautions.
The hazardous voltage input status LEDs on the RM-26999 will turn on (YELLOW) when a voltage is applied to the input channel(s) above 50 V DC or 40 V AC, 60 Hz. If the LED is off, a voltage above 50 V DC or 40 V AC, 60 Hz, has not been applied to the input channel and/or the terminal block is not powered on.
Minimum Required Competency
All persons involved with planning, installing, connecting, or configuring software and hardware for use in systems that employ the RM-26999 must meet the following minimum competency requirements:
- Be informed about dependencies, risks, and consequences associated with safe operation, failure, and unsafe system conditions of any system employing the RM-26999.
- Have appropriate training and knowledge in the operation and implementation of industrial processes, measurement and control, automation, electrical engineering, and safety compliance.
- Have sufficient knowledge of all applicable codes, laws, regulations, and standards.
- Be familiar with and have access to all requirements, conditions, specifications, and guidelines in all applicable NI documentation, including hardware documentation for the RM-26999 and the Data Acquisition equipment connected to the RM-26999.
User Responsibilities
- Read and adhere to all safety guidelines in the documentation for the RM-26999, accessories, and system components.
- Read the installation and configuration documentation for all hardware and software system components.
- Verify that all necessary system components and accessories are on hand.
- Mount, install, ground, and connect the hardware components of the system.
- Download, install, and configure all software components of the system.
- Verify cabling specifications and insulation meet all local codes for safe installation requirements.
- Conduct a system test to verify connectivity and functionality before connecting hazardous voltages.
- Follow all applicable codes, laws, regulations, and standards for workplace safety requirements when connecting, disconnecting, and configuring systems that measure hazardous voltages.