REM-11115 Specifications
- Updated2023-02-20
- 6 minute(s) read
REM-11115 Specifications
The following specifications are typical for the range -25 °C to 60 °C unless otherwise noted.
Analog Outputs
Number of outputs | 4 | ||||||||
D/A resolution | 16 bit | ||||||||
Representation of output values | 16 bits (15 bits + sign) | ||||||||
Process data update | 140 µs | ||||||||
Short-circuit and overload protection | Electronic | ||||||||
Transient protection | Suppressor diode | ||||||||
| |||||||||
|
Input Scaling
Hex | Dec | 0 V to 10 V | ±10 V | 0 V to 5 V | ±5 V | 0 mA to 20 mA | 4 mA to 20 mA |
---|---|---|---|---|---|---|---|
7FFF to 7F01 | — | 10.837 V | 10.837 V | 5.419 V | 5.419 V | 21.6747 mA | 21.3397 mA |
7F00 | 32512 | 10.837 V | 10.837 V | 5.419 V | 5.419 V | 21.6747 mA | 21.3397 mA |
7530 | 30000 | 10 V | 10 V | 5 V | 5 V | 20 mA | 20 mA |
3A98 | 15000 | 5 V | 5 V | 2.5 V | 2.5 V | 10 mA | 12 mA |
1 | 1 | 333.33 μV | 333.33 μV | 166.67 μV | 166.67 μV | 0.6667 μA | 4.0005333 mA |
0 | 0 | 0 V | 0 V | 0 V | 0 V | 0 mA | 4 mA |
FFFF | -1 | 0 V | -333.33 μV | 0 V | -166.67 μV | 0 mA | 4 mA |
C568 | -15000 | 0 V | -5 V | 0 V | -2.5 V | 0 mA | 4 mA |
8AD0 | -30000 | 0 V | -10 V | 0 V | -5 V | 0 mA | 4 mA |
8100 | -32512 | 0 V | -10.837 V | 0 V | -5.419 V | 0 mA | 4 mA |
80FF to 8000[1] | — | Hold last value | Hold last value | Hold last value | Hold last value | Hold last value | Hold last value |
8001 | Overrange | 10.837 V | 10.837 V | 5.419 V | 5.419 V | 21.6747 mA | 21.3397 mA |
8080 | Underrange | 0 V | -10.837 | 0 V | -5.419 V | 0 mA | Hold last value |
Power Requirements
Communications power from UBus | 5 VDC, via bus connector | ||||||
Current consumption from UBus | 120 mA, typical; 150 mA, maximum | ||||||
|
I/O Supply
Supply of analog output modules UA | 24 VDC (I/O supply and sensor supply) |
Maximum permissible voltage range | 19.2 VDC to 30 VDC (including all tolerances, including ripple) |
Current consumption from UA | 40 mA, typical (induced current consumption; no load, 0 V output); 60 mA, typical (4 voltage channels, 10 V output); 110 mA, maximum (4 current channels, 20 mA output, 500 Ω load) |
Surge protection | Electronic (35 V, 0.5 s) |
Polarity reversal protection | Polarity protection diode |
Protection | Suppressor diode |
External fuse rating | 8 A |
Remote I/O Local Bus
Connection method | Bus connector |
Transmission speed | 100 MBit/s |
Physical Characteristics
| |||||||||
Dimensions[2] | 126.1 mm (4.96 in.) × 35.0 mm(1.38 in.) × 54.0 mm (2.13 in.) | ||||||||
Weight[3] | 145 g (5.11 oz) |
Tolerance Data
The following specifications apply for tolerances at TA = 25 °C.
- Valid for nominal operation (UA = 24 V in the default configuration (unless documented otherwise).
- Typical data contains offset error, gain error, and linearity error in the respective default setting.
- All tolerances indicated as a percentage are related to the positive measuring range final value.
- Please also observe the values for temperature drift and the tolerances under influences of electromagnetic interferences.
- Additional tolerances may occur due to the influence of high-frequency electromagnetic interference caused by wireless transmission systems in the near vicinity. The values specified refer to nominal operation in the event of direct interference to components without additional shielding such as a steel cabinet.
- Tolerances can be reduced by providing further shielding measures for the I/O module such as a shielded control box/control cabinet.
Measurement Range | Absolute Tolerance | Relative Tolerance | ||
---|---|---|---|---|
Typical | Maximum | Typical | Maximum | |
0 V to 5 V, ±5 V, 0 V to 10 V, ±10 V | ±10 mV | ±30 mV | ±0.10% | ±0.30% |
0 mA to 20 mA, 4 mA to 20 mA | ±20 μA | ±60 μA | ±0.10% | ±0.30% |
Measurement Range | Drift[4] | |
---|---|---|
Typical | Maximum | |
0 V to 5 V, ±5 V, 0 V to 10 V, ±10 V | ±25 ppm/K | ±70 ppm/K |
0 mA to 20 mA, 4 mA to 20 mA | ±25 ppm/K | ±70 ppm/K |
|
Signal Rise Times
Load | Time for 0% to 99% |
---|---|
1 kΩ | 30 μs |
1 kΩ || 10 nF | 30 μs |
1 kΩ || 220 nF | 215 μs |
1 kΩ + 3 mH | 35 μs |
Load | Time for 0% to 99% |
---|---|
500 Ω | 125 μs |
500 Ω || 10 nF | 130 μs |
500 Ω || 220 nF | 300 μs |
500 Ω + 2 mH | 1 ms |
Isolation Withstand Voltages
Test section | Test voltage |
---|---|
5 V communications power (logic), 24 V supply (I/O) | 500 VAC, 50 Hz, 1 min. |
5 V supply (logic) / analog inputs | 500 VAC, 50 Hz, 1 min. |
5 V supply (logic) / functional earth ground | 500 VAC, 50 Hz, 1 min. |
24 V supply (I/O) / analog inputs | 500 VAC, 50 Hz, 1 min. |
24 V supply (I/O) / functional earth ground | 500 VAC, 50 Hz, 1 min. |
Analog inputs / functional earth ground | 500 VAC, 50 Hz, 1 min. |
Electromagnetic Compatibility
This product meets the requirements of the following EMC standards for electrical equipment.
- EN 61000-4-2 (IEC 61000-4-2): Electrostatic discharge (ESD); Criterion B; 6 kV contact discharge, 8 kV air discharge
- EN 61000-4-3 (IEC 61000-4-3): Electromagnetic fields; Criterion A; Field intensity: 10 V/m
- EN 61000-4-4 (IEC 61000-4-4): Fast transients (burst); Criterion B, 2 kV
- EN 61000-4-5 (IEC 61000-4-5): Transient surge voltage (surge); Criterion B; DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical); ±1 kV to shielded I/O cables
- EN 61000-4-6 (IEC 61000-4-6): Conducted interference; Criterion A; Test voltage 10 V
- EN 61000-6-2: Noise immunity
- EN 61000-6-3: Noise emission
- EN 55022: Radio interference properties; Class B
CE Compliance

- 2014/30/EU; Electromagnetic Compatibility Directive (EMC)
Shock and Vibration
Vibration resistance (EN/IEC 60068-2-6) | 5 g |
Shock (EN/IEC 60068-2-27) | 30 g |
Continuous shock (EN/IEC 60068-2-27) | 10 g |
Environmental
Operating temperature | -25 °C to 60 °C |
Storage temperature | -40 °C to 85 °C |
Ingress protection | IP20 |
Protection class | III, EN/IEC 61140, VDE 0140-1 |
Operating humidity | 5% to 95%, non-condensing |
Storage humidity | 5% to 95%, non-condensing |
Maximum altitude | 3,000 m |
Air pressure | 70 kPa to 106 kPa |
Indoor use only.