Property of DAQmx Trigger

Specifies the type of trigger to use to arm the task for a Start Trigger. If you configure an Arm Start Trigger, the task does not respond to a Start Trigger until the device receives the Arm Start Trigger.

Digital Edge (10150) Trigger on a rising or falling edge of a digital signal.
None (10230) Disable the trigger.
Time (15996) Trigger when a specified time is reached.

Remarks

The following table lists the characteristics of this property.

Permissionsread/write
Resettableyes
Settable while task is runningdevice-specific
Available in Run-Time Engineyes