NI-9472 Specifications
- Updated2024-11-25
- 6 minute(s) read
NI-9472 Specifications
Connector Types
The NI-9472 has more than one connector type: NI-9472 with screw terminal, NI-9472 with spring terminal, and NI-9472 with DSUB. Unless the connector type is specified, NI-9472 refers to all connector types.
Definitions
Warranted specifications describe the performance of a model under stated operating conditions and are covered by the model warranty.
Characteristics describe values that are relevant to the use of the model under stated operating conditions but are not covered by the model warranty.
- Typical specifications describe the performance met by a majority of models.
- Nominal specifications describe an attribute that is based on design, conformance testing, or supplemental testing.
Specifications are Typical unless otherwise noted.
Conditions
Specifications are valid for the range -40 °C to 70 °C unless otherwise noted. All voltages are relative to COM unless otherwise noted.
NI-9472 Pinout
Signal | Description |
---|---|
COM | Common reference connection to isolated ground |
DO | Digital output signal connection |
Vsup | Voltage supply connection |
LED Pattern | Indication |
---|---|
Solid | The channel has been programmed to be in the ON state. |
Off | The channel has been programmed to be in the OFF state. |
Output Characteristics
Number of channels | 8 digital output channels | ||||||||
Output type | Sourcing | ||||||||
Power-on output state | Channels off | ||||||||
External power supply voltage range (Vsup) | 6 VDC to 30 VDC | ||||||||
| |||||||||
Continuous output current (I0), per channel | 0.75 A maximum | ||||||||
Output voltage (V0) | Vsup - (I0 · R0) | ||||||||
|
Current | Channel Behavior | Module Protection |
---|---|---|
Less than .75 A | Channel does not trip | Module is not damaged |
.75 A to 1.5 A for 100 ms maximum, repeatable after 1 s[1]1 One channel at a time. | Channel does not trip | Module is not damaged |
1.5 A to 4.4 A | Channel does not trip | Module may be damaged |
4.4 A to 14 A | Channel may trip | Module may be damaged |
Greater than 14 A | Channel trips | Module is not damaged |
Output delay time (full load) | 100 µs maximum |
MTBF | 1,113,301 hours at 25 °C; Bellcore Issue 2, Method 1, Case 3, Limited Part Stress Method |
NI-9472 with Screw Terminal and Spring Terminal Safety Voltages
Connect only voltages that are within the following limits.
Channel-to-COM | 30 VDC maximum | ||||||||||||
|
Measurement Category II is for measurements performed on circuits directly connected to the electrical distribution system. This category refers to local-level electrical distribution, such as that provided by a standard wall outlet, for example, 115 V for U.S. or 230 V for Europe.
NI-9472 with DSUB Safety Voltages
Connect only voltages that are within the following limits.
Channel-to-COM | 30 VDC maximum | ||||||||||||
|
Measurement Category I is for measurements performed on circuits not directly connected to the electrical distribution system referred to as MAINS voltage. MAINS is a hazardous live electrical supply system that powers equipment. This category is for measurements of voltages from specially protected secondary circuits. Such voltage measurements include signal levels, special equipment, limited-energy parts of equipment, circuits powered by regulated low-voltage sources, and electronics.
Environmental Characteristics
| |||||||||||||
| |||||||||||||
Ingress protection | IP40 | ||||||||||||
Pollution Degree | 2 | ||||||||||||
| |||||||||||||
|
To meet these shock and vibration specifications, you must panel mount the system.
Power Requirements
| |||||||
|
Physical Characteristics
Dimensions | Visit ni.com/dimensions and search by module number. | ||||||||||||||
| |||||||||||||||
| |||||||||||||||
| |||||||||||||||
|
1 One channel at a time.