NI-9401
and sbRIO-9401 Specifications
Definitions
Warranted specifications describe the performance of a model under stated operating conditions and are covered by the model warranty.
Characteristics describe values that are relevant to the use of the model under stated operating conditions but are not covered by the model warranty.
- Typical specifications describe the performance met by a majority of models.
- Nominal specifications describe an attribute that is based on design, conformance testing, or supplemental testing.
Specifications are Typical unless otherwise noted.
Conditions
Specifications are valid for the range -40 °C to 70 °C unless otherwise noted. All voltages are relative to COM unless otherwise noted.
NI-9401
Pinout
Signal | Description |
---|---|
COM | Common reference connection to isolated ground |
DIO | Digital input/output signal connection |
NC | No connection |
Input/Output Characteristics
Number of channels | 8 DIO channels | ||||||||||||||||||||||||||||
Default power-on line direction | Input | ||||||||||||||||||||||||||||
Input/output type | TTL, single-ended | ||||||||||||||||||||||||||||
| |||||||||||||||||||||||||||||
| |||||||||||||||||||||||||||||
I/O propagation delay | 100 ns maximum | ||||||||||||||||||||||||||||
I/O pulse width distortion | 10 ns | ||||||||||||||||||||||||||||
Input current (0 V ≤ VIN ≤ 4.5 V ) | ±250 μA | ||||||||||||||||||||||||||||
Input capacitance | 30 pF | ||||||||||||||||||||||||||||
Input rise/fall time | 500 ns maximum | ||||||||||||||||||||||||||||
Overvoltage protection, channel-to-COM[2]2 Continued use at this level will degrade the life of the module. | ±30 V maximum on one channel at a time | ||||||||||||||||||||||||||||
MTBF | 1,244,763 hours at 25 °C; Bellcore Issue 2, Method 1, Case 3, Limited Part Stress Method |
Safety Voltages
Connect only voltages that are within the following limits:
| |||||||||||||
|
Measurement Category
Measurement Category I is for measurements performed on circuits not directly connected to the electrical distribution system referred to as MAINS voltage. MAINS is a hazardous live electrical supply system that powers equipment. This category is for measurements of voltages from specially protected secondary circuits. Such voltage measurements include signal levels, special equipment, limited-energy parts of equipment, circuits powered by regulated low-voltage sources, and electronics.
Environmental Characteristics
| |||||||||||||
| |||||||||||||
Ingress protection | IP40 | ||||||||||||
Pollution Degree | 2 | ||||||||||||
Maximum altitude | 2,000 m | ||||||||||||
|
To meet these shock and vibration specifications, you must panel mount the system.
Power Requirements
| |||||||
|
Physical Characteristics
Dimensions | Visit ni.com/dimensions and search by module number. |
Weight | 145 g (5.1 oz) |