NI-9350 Getting Started
- Updated2022-10-10
- 7 minute(s) read
NI-9350 Getting Started
NI-9350 Pinout
| Signal | Description |
|---|---|
| COM | Common reference connection |
| DI | Digital input signal connection |
| DO | Digital output signal connection |
| Vsup | Voltage supply connection |
NI-9350 LEDs
| LED | Description |
|---|---|
|
|
Vsup/Status |
| 0 | Internal Fault |
| 1 | I/O Fault |
| 2 | UserLED0 |
| LED | LED Color | LED Pattern | Indication |
|---|---|---|---|
| Vsup/Status | Green | On | Module is powered on. Module is in Operational Mode and User Program is running. |
| Flashing | Module powered on. Module is not in Operational Mode or User Program is not running. | ||
| Off | Module is powered off. | ||
| Internal Fault | Red | Flashing | Module is in Fail-safe Mode. |
| Off | Module is not in Fail-safe Mode. | ||
| I/O Fault | Red | Flashing | An I/O fault has been detected. |
| Off | No I/O Fault has been detected. | ||
| UserLED0 | Red | On | User-configurable. |
| Flashing | |||
| Off |
NI-9350 Block Diagram
Installing the Connector Backshell
- Align the connector backshell with the 26-pin spring terminal block.
- Secure the cable bundle to the connector backshell using a zip tie.
- Secure the connector backshell using the captive screws. Tighten to 0.5 N · m (4 lb · in.) torque.
Connecting an External Power Supply
You must connect an external power supply to the NI-9350. The module is independent from the chassis and requires an external power supply to operate.
Connect the positive lead of the power supply to the supply pin, Vsup, and the negative lead of the power supply to any common pin, COM.
The NI-9350 has current sourcing outputs, meaning the DO pin is driven to Vsup when the channel is turned on.
Functional Safety Editor I/O Configurations
Refer to the following diagrams to connect the NI-9350 based on the I/O configurations in the Functional Safety Editor. For more information about I/O Configurations, refer to the C Series Functional Safety Manual on ni.com/manuals.
NI-9350 Input Connection
- Use this diagram for single input and dual input configurations.
- Use one of the following pairs for dual switches: DI0 and DI1, DI2 and DI3, DI4 and DI5, or DI6 and DI7.
NI-9350 Single Input with Test Pulse Connection
- Use this diagram for single input with test pulse configurations.
- Use test pulses to detect wiring faults on NC (normally closed) switches.
- Connect the DO pin to the NC (normally closed) switch to provide test pulse output.
NI-9350 Dual Input with Test Pulse Connection
- Use this diagram for dual input with test pulse configurations.
- Use one of the following pairs for dual switches: DI0 and DI1, DI2 and DI3, DI4 and DI5, or DI6 and DI7.
- Use test pulses to detect wiring faults on NC (normally closed) switches.
NI-9350 Output Connection
- Use this diagram for the following configurations:
- Single output
- Dual output
- Single output with internal test pulse
- Dual output with internal test pulse
NI-9350 Output with External Test Pulse Connection
- Use this diagram for single output with external test pulse and dual output with external test pulse configurations.
- Connect a wire from the external monitoring location to a DI channel to monitor the test pulse.
- Connect the DI channel number that corresponds to the DO channel number. Single output with test pulse connections use DOn and DIn. Dual output with test pulse connections use DOn and DIn, DOn+1 and DIn+1.
NI-9350 Single Output with External Readback Connection
- Use this diagram for single output with external readback configurations.
- Connect a wire from the external monitoring location to a DI channel to monitor the output value.
NI-9350 Connection Guidelines
- Make sure that devices you connect to the NI-9350 are compatible with the module specifications.
- Connect one COM terminal for each DO and each DI connection until all COM terminals are populated. It is acceptable but not preferred to populate COM terminals with jumpers to meet this requirement.
- You must use a two-wire ferrule to create a secure connection when connecting two stranded wires to a single terminal.
- Push a solid wire or ferrule directly into the terminal.
- When inserting a stranded wire without a ferrule, first open the terminal by pressing the push button.
- Verify that all strands of a stranded wire are securely retained.
Power Supply
Users must use a limited power source (LPS) supply suitable to the safety needs and configuration of the implemented system. Implement one of the following options to ensure continued compliance with IEC 61010-1.
- The Vsup must be powered from a Class 2 or Limited Power Source (LPS), SELV source, 30 V DC maximum.
- The Vsup must be powered from a SELV source, 30 V DC maximum, with supplementary overcurrent protection in series, 8 A maximum breaking capacity at 120 s.
- The C Series Functional Safety module and associated controller must be installed in an end-use fire enclosure.
Pull-Down Resistor
- NI recommends connecting an external 3 kΩ pull-down resistor to each digital input channel in use.
- Resistor power must be rated at minimum to 300 mW at system ambient temperatures. A larger rating can increase reliability.
- A pull-down resistor reduces input signal response times when channels are driven by sourcing outputs.
- The user is responsible for evaluating and choosing the appropriate resistor and terminal block based on the system requirements.
- Follow mounting and thermal guidelines in the CompactRIO controller documentation.
Refer to the table below for suggested terminal blocks for mounting the resistor.
| Third Party Manufacturer | Series |
|---|---|
| Phoenix Contact | UTTB |
| Weidmuller | WTR |
Protecting the NI-9350 from Flyback Voltages
Install an external flyback diode on any digital output connection to inductive or energy-storing devices that do not have flyback protection. Inductive or energy storing devices include solenoids, motors, and relays.
High-Vibration Application Connections
If your application is subject to high vibration, NI recommends that you use ferrules to terminate stranded wire.
You must follow these guidelines to meet the shock and vibration performance specifications stated in the device datasheet on ni.com/manuals.
- Panel mount the system.
- Provide strain relief for the module by securing the cabling to a supporting fixture no more than 8 cm (3 in.) away from the opening of the connector backshell.
- Ensure that the supporting fixture for strain relief is stiff and rigidly coupled to the chassis mounting surface.
- Ensure that you do not directionally bias the module when applying strain relief.
Digital I/O Protection
The NI-9350 provides overcurrent and short-circuit protection for each DO channel.
Overtemperature Protection
The NI-9350 has an internal temperature sensor that will cause the module to enter Fail-safe Mode if the internal temperature limit is exceeded.
Implementing a Functional Safety System
This document provides information about connecting and installing the NI-9350 hardware. You must download a compiled User Program before deployment. For information about creating User Programs, deploying safety systems using the NI-9350, and diagnostics available on the NI-9350, go to ni.com/info and enter Info Code safetymanual.