NI 9155 Specifications
- Updated2023-02-17
- 5 minute(s) read
NI 9155 Specifications
This document lists the specifications for the NI 9155.
MXI-Express
Maximum cable length | 7 m |
Reconfigurable FPGA
FPGA type | Virtex-5 LX85 | ||||||||||||
Number of flip-flops | 51,840 | ||||||||||||
Number of 6-input LUTs | 51,840 | ||||||||||||
Number of DSP48 slices | 48 | ||||||||||||
Available block RAM | 3,456 kbits | ||||||||||||
Timebases | 40, 80, 120, 160, or 200 MHz | ||||||||||||
Accuracy | ±100 ppm (maximum) | ||||||||||||
|
Power Requirements
Voltage input range | 9 VDC to 30 VDC | ||||||
Maximum power input | 30 W | ||||||
|
Physical Characteristics
Screw-terminal wiring
Gauge | 0.2 mm 2 to 2.1 mm2 (24 AWG to 14 AWG) copper conductor wire | ||||||
Wire strip length | 6 mm (0.24 in.) of insulation stripped from the end | ||||||
Temperature rating | 85 °C | ||||||
Torque for screw terminals | 0.20 N · m to 0.25 N · m (1.8 lb · in. to 2.2 lb · in.) | ||||||
Wires per screw terminal | One wire per screw terminal | ||||||
Ferrules | |||||||
Weight | 1,600 g (56.4 oz) | ||||||
|
Safety Voltages
Connect only voltages that are within the following limits:
V terminal to C terminal | 30 VDC maximum, Measurement Category I |
Measurement Category I is for measurements performed on circuits not directly connected to the electrical distribution system referred to as MAINS voltage. MAINS is a hazardous live electrical supply system that powers equipment. This category is for measurements of voltages from specially protected secondary circuits. Such voltage measurements include signal levels, special equipment, limited-energy parts of equipment, circuits powered by regulated low-voltage sources, and electronics.
Hazardous Locations
U.S. (UL) | Class I, Division 2, Groups A, B, C, D, T4; Class I, Zone 2, AEx nA IIC T4 Gc |
Canada (C-UL) | Class I, Division 2, Groups A, B, C, D, T4; Ex nA IIC T4 Gc |
Europe (ATEX) and International (IECEx) | Ex nA IIC T4 Gc DEMKO 12 ATEX 1202658X IECEx UL 14.0089X |
Safety Compliance and Hazardous Locations Standards
This product is designed to meet the requirements of the following electrical equipment safety standards for measurement, control, and laboratory use:
- IEC 61010-1, EN 61010-1
- UL 61010-1, CSA C22.2 No. 61010-1
- EN 60079-0, EN 60079-7
- IEC 60079-0, IEC 60079-7
- UL 60079-0, UL 60079-7
- CSA C22.2 No. 60079-0, CSA C22.2 No. 60079-7
CE Compliance

- 2014/34/EU; Potentially Explosive Atmospheres (ATEX)
Electromagnetic Compatibility
- EN 61326-1 (IEC 61326-1): Class A emissions; Industrial immunity
Product Certifications and Declarations
Refer to the product Declaration of Conformity (DoC) for additional regulatory compliance information. To obtain product certifications and the DoC for NI products, visit ni.com/product-certifications, search by model number, and click the appropriate link.
Shock and Vibration
To meet these specifications, you must panel mount the system.
| |||||||
Operating shock | 30 g, 11 ms half sine; 50 g, 3 ms half sine; 18 shocks at 6 orientations |
Environmental
|
Ingress protection | IP40 |
Operating humidity (IEC 60068-2-56) | 10% RH to 90% RH, noncondensing |
Storage humidity (IEC 60068-2-56) | 5% RH to 95% RH, noncondensing |
Pollution Degree (IEC 60664) | 2 |
Maximum altitude | 2,000 m |
Indoor use only.
Environmental Management
NI is committed to designing and manufacturing products in an environmentally responsible manner. NI recognizes that eliminating certain hazardous substances from our products is beneficial to the environment and to NI customers.
For additional environmental information, refer to the Engineering a Healthy Planet web page at ni.com/environment. This page contains the environmental regulations and directives with which NI complies, as well as other environmental information not included in this document.
EU and UK Customers
电子信息产品污染控制管理办法(中国RoHS)
NI Services
Visit ni.com/support to find support resources including documentation, downloads, and troubleshooting and application development self-help such as tutorials and examples.
Visit ni.com/services to learn about NI service offerings such as calibration options, repair, and replacement.
Visit ni.com/register to register your NI product. Product registration facilitates technical support and ensures that you receive important information updates from NI.
NI corporate headquarters is located at 11500 N Mopac Expwy, Austin, TX, 78759-3504, USA.
In This Section
- MXI-Express
- Reconfigurable FPGA
- Power Requirements
- Physical Characteristics
- Safety Voltages
- Hazardous Locations
- Safety Compliance and Hazardous Locations Standards
- CE Compliance
- Electromagnetic Compatibility
- Product Certifications and Declarations
- Shock and Vibration
- Environmental
- Environmental Management
- EU and UK Customers
- 电子信息产品污染控制管理办法(中国RoHS)