cRIO-9805 Specifications
- Updated2023-12-05
- 2 minute(s) read
cRIO-9805 Specifications
Definitions
Warranted specifications describe the performance of a model under stated operating conditions and are covered by the model warranty.
Characteristics describe values that are relevant to the use of the model under stated operating conditions but are not covered by the model warranty.
- Typical specifications describe the performance met by a majority of models.
- Nominal specifications describe an attribute that is based on design, conformance testing, or supplemental testing.
Specifications are Typical unless otherwise noted.
Conditions
Specifications are valid for -40 °C to 70 °C unless otherwise noted.
Network Interface
Network ports used | TCP:830 (configuration only) TCP:2537 (configuration only) UDP:5353 (configuration only) TCP:5353 (configuration only) UDP:7865 (configuration only) UDP:8463 (configuration only) |
Network IP configuration | DHCP + Link-Local |
Ethernet
Number of ports | 4 ports, internally switched[1]1 This allows for line topologies or network redundancy. |
Network interface | 1000 Base-TX, full-duplex 1000 Base-TX,half-duplex 100 Base-TX, full-duplex 100 Base-TX, half-duplex 10 Base-T, full-duplex 10 Base-T, half-duplex |
Communication rates | 10/100/1000 Mbps, auto-negotiated |
Maximum cabling distance | 100 m/segment |
Maximum hops per line | 15 |
Timing and Synchronization
Protocol | IEEE 802.1AS for network synchronization over 1000 Base-TX, full-duplex |
Network synchronization accuracy | <1 μs |
Network synchronization accuracy with optimized configuration | <100 ns |
Power Requirements
Maximum power consumption | 5 W | ||||||
Power supply voltage | 9 V to 30 V | ||||||
| |||||||
|
Physical Characteristics
Weight | 406 g (14.3 oz) |
Dimensions | 30.0 mm × 88.1 mm × 106.9 mm (1.18 in. × 3.47 in. × 4.21 in.) |
Environmental Characteristics
Temperature and Humidity
| |||||||
| |||||||
Ingress protection | IP40 | ||||||
Pollution Degree | 2 | ||||||
Maximum altitude | 5,000 m |
Shock and Vibration
| |||||||
Operating shock | 30 g, 11 ms half sine; 50 g, 3 ms half sine; 18 shocks at 6 orientations |