cRIO-9064 Specifications

Definitions

Warranted specifications describe the performance of a model under stated operating conditions and are covered by the model warranty.

Characteristics describe values that are relevant to the use of the model under stated operating conditions but are not covered by the model warranty.

  • Typical specifications describe the performance met by a majority of models.
  • Nominal specifications describe an attribute that is based on design, conformance testing, or supplemental testing.

Specifications are Typical unless otherwise noted.

Conditions

Specifications are valid for -20 °C to 55 °C unless otherwise noted.

Processor

Type

Xilinx Zynq-7000, XC7Z020 All Programmable SoC

Architecture

ARM Cotex-A9

Speed

667 MHz

Cores

2

Flash reboot endurance[1]1 You can increase the flash reboot endurance value by performing field maintenance on the device. If you expect that your application may exceed the maximum cycle count listed in this document, contact NI support for information about how to increase the reboot endurance value.

100,000 cycles

Operating System

Note For minimum software support information, visit ni.com/info and enter the Info Code swsupport.

Supported operating system

NI Linux Real-Time (32-bit)

Software requirements
Application software

LabVIEW

LabVIEW 2014 SP1 or later, LabVIEW Real-Time Module 2014 SP1 or later, LabVIEW FPGA Module 2014 SP1 or later [2]2 LabVIEW FPGA Module is not required when using Scan Interface mode. To program the user-accessible FPGA on the cRIO-9064, LabVIEW FPGA Module is required.

Driver software

NI-RIO Device Drivers 14.5 or later

Memory

Nonvolatile memory[3]3 Formatted capacity of nonvolatile memory may be slightly less than this value.

1 GB

Volatile memory (DRAM)

512 MB

Network

Network interface

10Base-T, 100Base-T, 1000Base-T Ethernet

Compatibility

IEEE 802.3

Communication rates

10 Mb/s, 100 Mb/s, 1,000 Mb/s auto-negotiated, half/full-duplex

Maximum cabling distance

100 m/segment

Internal Real-Time Clock

Accuracy

5 ppm

USB Ports

USB device port

Type

USB 2.0 Hi-Speed, with standard B connector

Maximum data rate

480 Mb/s

USB host port

Type

USB 2.0 Hi-Speed, with standard A connector

Maximum data rate

480 Mb/s

Reconfigurable FPGA

Type

Xilinx Zynq-7000, XC7Z020 All Programmable SoC

Number of logic cells

85,000

Number of flip-flops

106,400

Number of 6-input LUTs

53,200

Number of DSP slices (18 × 25 multipliers)

220

Available block RAM

4,480 kbits

Number of DMA channels

16

Number of logical interrupts

32

Battery

Note The battery is not user-replaceable. Refer to the cRIO-9064 Safety, Environmental, and Regulatory Information document for information about replacing the battery.
Note Battery life may drop dramatically in extreme temperatures.

Typical battery life with power applied to power connector

10 years

Typical battery life in storage at 55 °C

5 years

Power Requirements

Voltage input range

9 V DC to 30 V DC

Reverse-voltage protection

30 V DC maximum

Maximum power input, with four C Series modules

18 W

Maximum power input, without C Series modules

14 W

Physical Characteristics

Dimensions and Weight

Dimensions

178.1 mm × 87.3 mm × 64.3 mm

(7.01 in. × 3.44 in. × 2.63 in.)

Weight

692 g (24.39 oz)

Screw Terminal Wiring

Gauge

0.2 mm2 to 2.1 mm2 (24 AWG to 14 AWG) copper conductor wire

Wire strip length

6 mm (0.24 in.) of insulation stripped from the end

Temperature rating

85 °C

Torque for screw terminals

0.20 N · m to 0.25 N · m

(1.8 lb · in. to 2.2 lb · in.)

Wires per terminal

One wire per screw terminal

Connector securement

Securement type

Screw flanges provided

Torque for screw flanges

0.3 N · m to 0.4 N · m

(2.7 lb · in. to 3.5 lb · in.)

Safety Voltages

Connect only voltages that are within the following limits:

V terminal to C terminal

30 V DC maximum, Measurement Category I

Measurement Category

Caution Do not connect the product to signals or use for measurements within Measurement Categories II, III, or IV.
Attention Ne pas connecter le produit à des signaux dans les catégories de mesure II, III ou IV et ne pas l'utiliser pour effectuer des mesures dans ces catégories.
Warning Do not connect the product to signals or use for measurements within Measurement Categories II, III, or IV, or for measurements on MAINs circuits or on circuits derived from Overvoltage Category II, III, or IV which may have transient overvoltages above what the product can withstand. The product must not be connected to circuits that have a maximum voltage above the continuous working voltage, relative to earth or to other channels, or this could damage and defeat the insulation. The product can only withstand transients up to the transient overvoltage rating without breakdown or damage to the insulation. An analysis of the working voltages, loop impedances, temporary overvoltages, and transient overvoltages in the system must be conducted prior to making measurements.
Mise en garde Ne pas connecter le produit à des signaux dans les catégories de mesure II, III ou IV et ne pas l'utiliser pour des mesures dans ces catégories, ou des mesures sur secteur ou sur des circuits dérivés de surtensions de catégorie II, III ou IV pouvant présenter des surtensions transitoires supérieures à ce que le produit peut supporter. Le produit ne doit pas être raccordé à des circuits ayant une tension maximale supérieure à la tension de fonctionnement continu, par rapport à la terre ou à d'autres voies, sous peine d'endommager et de compromettre l'isolation. Le produit peut tomber en panne et son isolation risque d'être endommagée si les tensions transitoires dépassent la surtension transitoire nominale. Une analyse des tensions de fonctionnement, des impédances de boucle, des surtensions temporaires et des surtensions transitoires dans le système doit être effectuée avant de procéder à des mesures.

Measurement Category I is for measurements performed on circuits not directly connected to the electrical distribution system referred to as MAINS voltage. MAINS is a hazardous live electrical supply system that powers equipment. This category is for measurements of voltages from specially protected secondary circuits. Such voltage measurements include signal levels, special equipment, limited-energy parts of equipment, circuits powered by regulated low-voltage sources, and electronics.

Note Measurement Categories CAT I and CAT O are equivalent. These test and measurement circuits are for other circuits not intended for direct connection to the MAINS building installations of Measurement Categories CAT II, CAT III, or CAT IV.

Environmental

Temperature

Operating

-20 °C to 55 °C

Storage

-40 °C to 85 °C

Humidity

Operating

10% RH to 90% RH, noncondensing

Storage

5% RH to 95% RH, noncondensing

Ingress protection

IP40

Pollution Degree

2

Maximum altitude

5,000 m

Shock and Vibration
Operating vibration

Random

5 g RMS, 10 Hz to 500 Hz

Sinusoidal

5 g, 10 Hz to 500 Hz

Operating shock

30 g, 11 ms half sine; 50 g, 3 ms half sine; 18 shocks at 6 orientations

Notice Use NI-9917 and NI-9918 industrial enclosures to protect the cRIO-9064 in harsh, dirty, or wet environments

To meet the shock and vibration specifications, you must mount the cRIO-9064 system directly on a flat, rigid surface as described in the user manual, affix ferrules to the ends of the terminal wires, install an SD card cover (SD Door Kit, 783660-01), and use retention accessories for the USB host ports (NI Industrial USB Extender Cable, 152166-xx), USB device port (NI Locking USB Cable, 157788-01), and mini DisplayPort connector (NI Retention Accessory for Mini DisplayPort, 156866-01). All cabling should be strain-relieved near input connectors. Take care to not directionally bias cable connectors within input connectors when applying strain relief.

1 You can increase the flash reboot endurance value by performing field maintenance on the device. If you expect that your application may exceed the maximum cycle count listed in this document, contact NI support for information about how to increase the reboot endurance value.

2 LabVIEW FPGA Module is not required when using Scan Interface mode. To program the user-accessible FPGA on the cRIO-9064, LabVIEW FPGA Module is required.

3 Formatted capacity of nonvolatile memory may be slightly less than this value.