Product Descriptions

cDAQ-9181: 1‑Slot, Ethernet CompactDAQ Chassis

cDAQ-9185: 4-Slot, TSN-Enabled Ethernet CompactDAQ Chassis

cDAQ-9189: 8-Slot, TSN-Enabled Ethernet CompactDAQ Chassis

Physical Characteristics

Weight

cDAQ-9181

470 g (16.6 oz)

cDAQ-9185

660.5 g (23.3 oz)

cDAQ-9189

1,065.9 g (37.6 oz)

Dimensions (unloaded)

cDAQ-9181

194.0 mm × 88.7 mm × 33.6 mm (7.64 in. × 3.49 in. × 1.32 in.)

cDAQ-9185

178.1 mm × 88.1 mm × 64.1 mm (7.01 in. × 3.47 in. × 2.52 in.)

cDAQ-9189

272.8 mm × 88.1 mm × 62.3 mm (10.74 in. × 3.47 in. × 2.45 in.)

cDAQ-9181 Power Connector

Screw-terminal wiring

Gauge

0.5 mm2 to 2.1 mm2 (20 AWG to 14 AWG) copper conductor wire

Wire strip length

6 mm (0.24 in.) of insulation stripped from the end

Temperature rating

85 °C

Torque for screw terminals

0.20 N · m to 0.25 N · m (1.8 lb · in. to 2.2 lb · in.)

Wires per screw terminal

One wire per screw terminal

Connector securement

Securement type

Screw flanges provided

Torque for screw flanges

0.20 N · m to 0.25 N · m (1.8 lb · in. to 2.2 lb · in.)

cDAQ-9185/9189 Power Connector

Screw-terminal wiring

Gauge

0.2 mm2 to 2.1 mm2 (24 AWG to 14 AWG) copper conductor wire

Wire strip length

6 mm (0.24 in.) of insulation stripped from the end

Temperature rating

85 °C

Torque for screw terminals

0.20 N · m to 0.25 N · m (1.8 lb · in. to 2.2 lb · in.)

Wires per screw terminal

One wire per screw terminal

Connector securement

Securement type

Screw flanges provided

Torque for screw flanges

0.3 N · m to 0.4 N · m (2.7 lb · in. to 3.5 lb · in.)

Environmental

Operating temperature

cDAQ-9181

0 °C to 55 °C

cDAQ-9185

-40 °C to 70 °C

cDAQ-9189

-40 °C to 70 °C

Note Failure to follow the mounting instructions in the user manual can cause temperature derating.
Storage temperature

cDAQ-9181

-10 °C to 70 °C

cDAQ-9185

-40 °C to 85 °C

cDAQ-9189

-40 °C to 85 °C

Ingress protection

cDAQ-9181

IP30

cDAQ-9185

IP40

cDAQ-9189

IP40

Operating humidity

10% RH to 90% RH, noncondensing

Storage humidity

5% RH to 95% RH, noncondensing

Pollution Degree

2

Maximum altitude

5,000 m

Indoor use only.

Hazardous Locations

Explosive atmospheres rating

Ex ec IIC T4 Gc

CCC certificate number

2021312310000336

Safety Guidelines

Operate the product only as described in this document.

Caution This icon denotes a caution, which advises you to consult documentation where this symbol is marked.
Caution Do not operate this product in a manner not specified in this document. Product misuse can result in a hazard. You can compromise the safety protection built into the product if the product is damaged in any way. If the product is damaged, return it to NI for repair.

Safety Guidelines for Hazardous Locations

The cDAQ-9181 has been evaluated as Ex ec IIC T4 Gc equipment and is CCC certified. Each product is suitable for use within ambient temperatures of 0 °C ≤ Ta ≤55 °C in either nonhazardous locations or Zone 2 hazardous locations.

The cDAQ-9185/9189 have been evaluated as Ex ec IIC T4 Gc equipment and are CCC certified. Each product is suitable for use within ambient temperatures of -40 °C ≤ Ta ≤70 °C in either nonhazardous locations or Zone 2 hazardous locations.

Follow these guidelines if you are installing the product in a potentially explosive environment. Not following these guidelines may result in serious injury or death.

Caution Do not disconnect the power supply wires and connectors from the controller unless power has been switched off.
Caution Do not disconnect I/O‐side wires or connectors unless power has been switched off or the area is known to be nonhazardous.
Caution Do not remove modules unless power has been switched off or the area is known to be nonhazardous.
Caution Substitution of components may impair suitability for Zone 2.
Caution The system shall only be used in an area of not more than Pollution Degree 2, as defined in IEC/EN 60664-1.
Caution The system shall be mounted in a CCC-certified enclosure with a minimum ingress protection rating of at least IP54 as defined in GB/T3836.1.
Caution The enclosure must have a door or cover accessible only by the use of a tool.
Caution You must make sure that transient disturbances do not exceed 140% of the rated voltage.
Caution (cDAQ-9181) When operating the product in hazardous locations, you must use the power connector with a power supply rated for hazardous locations. The power supply included in the kit is not hazardous locations-certified. Visit ni.com to find hazardous locations-certified power supplies.

Safety Voltages

Connect only voltages that are within the following limits:

V terminal to C terminal

30 V maximum, Measurement Category I

Caution Do not connect the product to signals or use for measurements within Measurement Categories II, III, or IV.

Power Requirements

cDAQ-9181

Voltage input range

9 V to 30 V

Maximum power consumption

5 W

cDAQ-9185/9189

Voltage input range

9 V to 30 V

Maximum power consumption

16 W

Installing C Series Modules

Verify that power is not connected to the I/O connector(s) on the C Series module.

Removing C Series Modules

Verify that power is not connected to the I/O connector(s) on the C Series module before you remove a module from the chassis.

Safety Compliance and Hazardous Locations Standards

This product is designed to meet the requirements of the following electrical equipment safety standards for measurement, control, and laboratory use:

  • IEC 61010-1
  • IEC 60079-0, IEC 60079-7
  • GB/T3836.1, GB/T3836.3
Note For safety certifications, refer to the product label or the Product Certifications and Declarations section.