C Series Functional Safety Firmware
- Updated2024-05-17
- 1 minute(s) read
C Series Functional Safety Firmware
Firmware Release Versions
The following sections detail the C Series Functional Safety Firmware releases and associated known issues. You can read the firmware version through Scan Interface. To determine the firmware version, add a Property Node to your monitoring VI in LabVIEW.
Caution You must verify and formally document that your safety application is not affected by the known issues documented below.
Module | Version | Date Released | Notes |
---|---|---|---|
NI 9350 | 0x17081412 | September 2017 | This version shipped with the initial release of the NI 9350. |
0x18010811 | March 2018 | This version implements a fix for undetected faults when driving heavy loads. | |
NI 9351 | 0x18031516 | May 2018 | This version shipped with the initial release of the NI 9351. |
Known Issue | Version Affected | ||
---|---|---|---|
0x17081412 | 0x18010811 | 0x18031516 | |
Open circuit faults on digital outputs | ✔ | ✔ | |
Passthrough value behavior | ✔ | ✔ | |
Overcurrent on dual digital inputs with test pulses | ✔ | ✔ | ✔ |
Undetected faults when driving heavy loads | ✔ |