Product Descriptions
- Updated2022-05-02
- 7 minute(s) read
Product Descriptions
NI-9203: 200 kS/s, ±20 mA, 8-Channel C Series Current Input Module
NI-9208: 500 S/s, ±20 mA, 16-Channel C Series Current Input Module
NI-9253: 50 kS/s/ch, ±20 mA, 24-Bit, 8-Channel C Series Current Input Module
Physical Characteristics
| |||||||||||||
Dimensions | Visit ni.com/dimensions and search by module number. |
NI-9203 with Screw Terminal
| |||||||||||||
|
NI-9203 with Spring Terminal
| |||||||||||||
|
NI-9208 with Spring Terminal
| |||||||||||||
|
NI-9253 with Spring Terminal
| |||||||||||||||||||||
|
Environmental
| |||||||||||
Ingress protection | IP40 | ||||||||||
| |||||||||||
Pollution Degree | 2 | ||||||||||
|
Indoor use only.
Hazardous Locations
Explosive atmospheres rating | Ex ec IIC T4 Gc |
CCC certificate number | 2021312310000312 |
Safety Guidelines
Operate the product only as described in this document.
Safety Guidelines for Hazardous Voltages
(Screw Terminal and Spring Terminal Products)
If hazardous voltages are connected to the device, take the following precautions. A hazardous voltage is a voltage greater than 42.4 V peak voltage or 60 V DC to earth ground.
You may connect signals which may be floating at hazardous voltages only to the products with screw terminal or spring terminal connectors. Do not connect signals which may be floating at hazardous voltages to the products with DSUB connectors.
Safety Guidelines for Hazardous Locations
These products have been evaluated as Ex ec IIC T4 Gc equipment and are CCC certified. Each product is suitable for use within ambient temperatures of -40 °C ≤ Ta ≤ 70 °C in either nonhazardous locations or Zone 2 hazardous locations. If you are using the products in Gas Group IIC hazardous locations, you must use the device in an NI chassis that has been evaluated as Ex ec IIC T4 Gc equipment.
Follow these guidelines if you are installing the product in a potentially explosive environment. Not following these guidelines may result in serious injury or death.
Safety Voltages
NI-9203
Connect only voltages that are within the following limits:
Maximum voltage, Channel-to-COM | ±30 V DC maximum | ||||||||||||||||||
Channel-to-channel isolation | None | ||||||||||||||||||
|
NI-9208 with Spring Terminal
Connect only voltages that are within the following limits:
Maximum voltage, Channel-to-COM | ±30 V DC maximum | ||||||||||||
|
NI-9208 with DSUB
Connect only voltages that are within the following limits:
Maximum voltage, Channel-to-COM | ±30 V DC maximum | ||||||||||||
|
NI-9253
Connect only voltages that are within the following limits:
AI-to-COM and Vsup-to-COM | ±30 V DC maximum | ||||||
Channel-to-channel isolation | None | ||||||
| |||||||
Overvoltage protection | ±30 V, between any two pins of the connector[2]2 Only 1 channel at a time. |
Installing C Series Modules
Verify that power is not connected to the I/O connector(s) on the C Series module.
Removing C Series Modules
Verify that power is not connected to the I/O connector(s) on the C Series module before you remove a module from the chassis.
Safety Compliance and Hazardous Locations Standards
This product is designed to meet the requirements of the following electrical equipment safety standards for measurement, control, and laboratory use:
- IEC 61010-1
- IEC 60079-0, IEC 60079-7
- GB/T3836.1, GB/T3836.3
Product Certifications and Declarations
To obtain product certifications and the DoC for NI products, visit ni.com/product-certifications, search by model number, and click the appropriate link.
Worldwide Support and Services
NI corporate headquarters is located at 11500 North Mopac Expressway, Austin, Texas, 78759-3504, USA.