Obejectname (.cbx) | Filename (.ini) | Sectionname | Keyname [=default value] | Description |
allbrad.cbx | allbrad.ini | [PLC2] | UnprotectedWrite= | To disable an STS error reported by the Allen Bradley PLC when trying to write to protected registers on the PLC. It allows writing to protected registers. For example: [PLC2] Unprotected Write=yes |
| allbrad.ini | [KT] | TranslateLogical Address= | Converts logical address to physical (See DF1 protocol specification; Chapter: PLC-2 physical Addressing). For example: [KT] TranslateLogical Address=yes |
daniel.cbx | daniel.ini | [all]/[objname] | UpdateOutputs=100 | Sets the amount of polls to skip an output update. |
| daniel.ini | [all]/[objname] | RefreshOutputs=1 | Sets to refresh all outputs every UpdateOutput polls. |
| daniel.ini | [all]/[objname] | SkipImmediatePoll=0 | Sets to poll immediately upon getting a connection. |
| daniel.ini | [all]/[objname] | ConfirmPoll=0 | Sets to poll immediately to confirm writes. |
| daniel.ini | [all]/[objname] | SkipPollBefore Write=0 | Sets to skip a read poll before write (could be TRUE, in case of ConfirmPoll TRUE). |
| daniel.ini | [All] | MaxChannels=8 | Sets max number of paths that can be open. |
devnet.cbx | devnet.ini | [all] | StartupDelay=10 | Number of seconds to delay before first poll to device; default is 10 secs. For example: [all] StartupDelay=20 |
fpoint.cbx | fpoint.ini | [objname] | FilterChAlarms=0 | Filters several alarms coming from the FieldPoint driver: FP module - channel status - Error message FP-AI-1xx - 1 - Out of range FP-AO-200 - 1 - Open Current Loop FP-AO-210 - 1 - Overcurrent Protection FP-DO-410 - 1 - Current Limited FP-TC-120 - 1 - Out of Range FP-RTD-122 - 1 - Out of Range FP-CTR-500 - 1 - Overflow since Last Read For example: [FieldPoint1] FilterChAlarms=1 |
ge.cbx | ge.ini | [ge]/[objname] | OkToWriteUnchanged Values=0 | Specifies to perform block writes. For example: [GE1] OkToWrite Unchanged Values=1 |
hitachie.cbx1 | hitachie.ini | [ethernet] | DiagnosticPath= | Creates a diagnostic file for Ethernet communication. For example: [ethernet] DiagnosticPath= c:\temp\ hitachiediag.txt |
modbus.cbx | modbus.ini | [ethernet] | DiagnosticPath= | Creates a diagnostic file for Ethernet communication. For example: [ethernet] DiagnosticPath= c:\temp\ modbusdiag.txt |
| modbus.ini | [all]/[objname] | UpdateOutputs=100 | Sets the amount of polls to skip an output update. |
| modbus.ini | [all]/[objname] | RefreshOutputs=1 | Sets to refresh all outputs every UpdateOutput polls. |
| modbus.ini | [all]/[objname] | SkipImmediatePoll=0 | Sets to poll immediately upon getting a connection. |
| modbus.ini | [all]/[objname] | AlwaysWrite=0 | Sets to always write redundant writes. |
| modbus.ini | [all]/[objname] | OptimizeWrite=0 | Sets to write Coils/Register optimized. |
| modbus.ini | [all]/[objname] | Protocol=RTU | Sets protocol mode; RTU or ASCII. For example: [Modbus1] Protocol=ASCII |
| modbus.ini | [All] | MaxChannels=8 | Sets max number of paths that can be open. |
mtsbshi.cbx | mtsbshi.ini | [all]/[objname] | UpdateOutputs=100 | Sets the amount of polls to skip an output update. |
| mtsbshi.ini | [all]/[objname] | RefreshOutputs=1 | Sets to refresh all outputs every UpdateOutput polls. |
nif.cbx2 | lookout.ini | [Fieldbus] | AlarmPriority=0 | Alarm priority for Fieldbus objects. (default = 0) |
optohost.cbx | optohost.ini | [Diagnostics] | TransactionFile= | Creates a diagnostic file for Ethernet communication. |
optomist.cbx | optomist.ini | [all]/[objname] | UpdateWrites=0 | Sets to refresh all outputs every 100 polls. |
s5as511.cbx2 | lookout.ini | [S5-AS511] | Diagnostics=0 | Turns on diagnostic recording functions in S5-AS511 driver. When activated, this option logs diagnostic information to the s5as511.dai file in the Lookout directory. =0 diagnostics are off (default) =1 diagnostics are on |
s7_hmi.cbx2 | s7_hmi.ini | [COMx] x=1.. | MPIBaud=Auto | Specifies the speed at which the MPI Network is operating. These selections are possible. "187.5K", "Auto". For example: [COM2] MPIBaud=Auto HighestMPI=68 PanelMPI=34 |
| s7_hmi.ini | [COMx] x=1.. | HighestMPI=31 | The highest possible MPI address for any device on the network. The range for this setting is from 0 to 126; the default is 31. |
| s7_hmi.ini | [COMx] x=1.. | PanelMPI= | The MPI address assigned to the hardware adapter that is being used to talk to the network. The range for this setting is from 0 to the HighestMPI setting. |
siemens.cbx | siemens.ini | [objname] | InitTimeout=2 | Sets the time that the application association will lock out other block's calls to funcs like tf_receive and tf_send; 1..10 seconds. For example: [PLC1] InitTimeout=3 |
sixnet.cbx2 | lookout.ini | [Sixnet] | IOMAPAlarm Priority=5 | Priority of the "Unable to load Sixnet IOMAP library: iobase32.dll" alarm in Sixnet. (default = 5) |
| lookout.ini | | ProjectAlarm Priority=5 | Priority of the "No Sixnet configuration currently loaded" alarm in Sixnet. (default = 5) |
squared.cbx | squared.ini | [all] | Bit1Addressing | Sets bit addressing to 1-16 instead of 0-15. For example: [SquareD1] Bit1Addressing=1 |
| squared.ini | [ethernet] | DiagnosticFile= | Creates a diagnostic file for Ethernet communication. For example: [SquareD1] DiagnosticFile= c:\temp\ squareddiag.txt |
tesco.cbx | tesco.ini | [Diagnostics] | DiagnosticFile= | Creates a diagnostic file for Tesco communication. |
| tesco.ini | [Diagnostics] | Setpoint=0 | Turns on Setpoint logs for DiagnosticFile. |
| tesco.ini | [Diagnostics] | GeneralComm=0 | Turns on GeneralComm logs for DiagnosticFile. |
| tesco.ini | [All]/[objname] | SPDeviation=0 | A deviation for setpoint writes. |
tiway.cbx | lookout.ini | [Tiway] | DiagnosticFile= | Creates a diagnostic file for Tiway communication. For example: [Tiway] DiagnosticFile= c:\temp\ tiwaydiag.txt |
| lookout.ini2 | [Tiway]/[objname] | UpdateOutputs=100 | Sets to refresh all outputs every UpdateOutputs polls (=0 disables to refresh all outputs). |
| lookout.ini | [objname] | ConfirmPoll=0 | Sets to do a confirm poll, in addition it will skip doing the poll before the write. |
| tiway.ini | [PCAcardx] x=1..4 | BaseAddress= | Sets base address for the cards can be set anywhere from 0x8000 to 0xFF00 (DOS area: 0xA000..0xEF00) NOTE: BaseAddress and Irq are not required to be set in .ini because the driver searches automatically for it. However, if you set it in the .ini, the object uses those settings. It assumes that PCAcard1 has the lowest base address and so on. |
| tiway.ini | [PCAcardx] x=1..4 | Irq= | Sets IRQ for the PC Adapter cards and can be anywhere from 1..15 (0=No IRQ). NOTE: BaseAddress and Irq are not required to be set in .ini because the driver searches automatically for it. However, if you set it in the .ini, the object uses those settings. |
| tiway.ini3 | [SFx] x=1.. | macro-string | Configure Store and forward macros into Tiway structure (See SIEMENS TIWAY Host Adapter Card Manual). For example: [SF1] <C/V> <source-offset> <count> <msec> <dest-block> <dest-offset> |
| tiway.ini3 | [UHA1COMx] x=1.. [PCAcardx] x=1.. | Optionxx=0xFFFF | Read Host Adapter command 30 (configure network manager) optional settings. Network manager configuration options ( 00 - 0E (00 unused)): xx=01..0E (See SIEMENS TIWAY Host Adapter Card Manual) |
vmax.cbx | vmax.ini | [ethernet] | DiagnosticPath= | Creates a diagnostic file for Ethernet communication. For example: [ethernet] DiagnosticPath= c:\temp\ vmaxdiag.txt |