Specifications
- Updated2023-02-19
- 8 minute(s) read
Specifications
This document contains specifications for the PXIe-1084 chassis.
Electrical
The following section provides information about the PXIe-1084 AC input and DC output.
AC Input
Input rating | 100 to 240 VAC, 50/60 Hz, 10 to 5 A, 100 to 120 VAC, 400 Hz, 10 A |
Operating voltage range[1] | 90 to 264 VAC |
Nominal input frequency | 50 Hz/60 Hz/400 Hz[2] |
Operating frequency range[1] | 47 to 440 Hz |
Efficiency | 85% typical |
Over-current protection | Internal fuse in line |
Main power disconnect | The AC power cable provides main power disconnect. Do not position the equipment so that it is difficult to disconnect the power cord. The front-panel power switch causes the internal chassis power supply to provide DC power to the PXI Express backplane. With the Timing and Synchronization upgrade, you can use the rear-panel 15-pin connector and inhibit mode switch to control the internal chassis power supply. |
DC Output
DC output characteristics of the PXIe-1084.
Voltage Rail | Maximum Current | Load Regulation | Maximum Ripple and Noise (20 MHz BW) |
---|---|---|---|
+5V_AUX | 4.1 A | ±5% | 50 mVpp |
+12 V | 54.1 A | ±5% | 100 mVpp |
+5 V | 51.1 A | ±5% | 50 mVpp |
+3.3 V | 60 A | ±5% | 50 mVpp |
-12 V | 4.25 A | ±5% | 50 mVpp |
Maximum total available power for the PXIe-1084 is 650 W.
Slot | +5 V | V (I/O) | +3.3 V | +12 V | -12 V | 5 VAUX |
---|---|---|---|---|---|---|
PXI Express System Controller Slot | 9 A | - | 9 A | 20 A | - | 2 A |
Hybrid Peripheral Slot with PXI-5 Peripheral | - | - | 6 A | 6 A | - | 1 A |
Hybrid Peripheral Slot with PXI-1 Peripheral | 6 A | 5 A | 6 A | 1 A | 1 A | - |
Over-current protection | All outputs protected from short circuit and overload with automatic recovery |
Over-voltage protection | +12 V, +5 V, and +3.3 V clamped at 20 to 30% above nominal output voltage |
Chassis Cooling
Module cooling | Forced air circulation (positive pressurization) through three 210 CFM fans with High/Auto speed selector | ||||||||
Module slot airflow direction | Bottom of module to top of module | ||||||||
Module intake | Bottom rear of chassis | ||||||||
Module exhaust | Top of chassis | ||||||||
Slot cooling capacity | 58 W | ||||||||
Secondary cooling | Forced air circulation (positive pressurization) through one 70 CFM fan | ||||||||
Side intake | Right side of chassis | ||||||||
Side exhaust | Left side of chassis | ||||||||
Power supply cooling | Forced air circulation through two integrated fans | ||||||||
Power supply intake | Top rear of chassis | ||||||||
Power supply exhaust | Top of chassis | ||||||||
Timing and Synchronization upgrade intake | Right side of chassis | ||||||||
Timing and Synchronization upgrade exhaust | Top of chassis | ||||||||
|
Environmental
Maximum altitude | 2,000 m (6,560 ft.), 800 mbar (at 25 °C ambient) |
Pollution Degree | 2 |
Indoor use only.
Operating Environment
| |||||||
Relative humidity range | 10% to 90%, noncondensing (IEC 60068-2-78.)[3] |
Storage Environment
Ambient temperature range | –40 °C to 71 °C (IEC-60068-2-1 and IEC-60068-2-2.)3 Meets MIL-PRF-28800F Class 3 limits. |
Relative humidity range | 5% to 95%, noncondensing (IEC-60068-2-78.)3 |
Shock and Vibration
Operational shock | 30 g peak, half-sine, 11 ms pulse (IEC-60068-2-27.)3 Meets MIL-PRF-28800F Class 2 limits. |
Operational random vibration | 5 to 500 Hz, 0.3 grms |
Non-operating vibration | 5 to 500 Hz, 2.4 grms (IEC 60068-2-64.)3 Non-operating test profile exceeds the requirements of MIL-PRF-28800F, Class 3. |
Acoustic Emissions
Sound Pressure Level (at Operator Position)
(Tested in accordance with ISO 7779. Meets MIL-PRF-28800F requirements.)
|
|
Sound Power Level
|
|
Safety
This product is designed to meet the requirements of the following electrical equipment safety standards for measurement, control, and laboratory use:
- IEC 61010-1, EN 61010-1
- UL 61010-1, CSA 61010-1
Electromagnetic Compatibility
This product meets the requirements of the following EMC standards for electrical equipment for measurement, control, and laboratory use:
- EN 61326-1 (IEC 61326-1): Class A emissions; Basic immunity
- EN 55011 (CISPR 11): Group 1, Class A emissions
- EN 55022 (CISPR 22): Class A emissions
- EN 55024 (CISPR 24): Immunity
- AS/NZS CISPR 11: Group 1, Class A emissions
- AS/NZS CISPR 22: Class A emissions
- FCC 47 CFR Part 15B: Class A emissions
- ICES-001: Class A emissions
CE Compliance

This product meets the essential requirements of applicable European Directives, as follows:
- 2014/35/EU; Low-Voltage Directive (safety)
- 2014/30/EU; Electromagnetic Compatibility Directive (EMC)
Online Product Certification
Refer to the product Declaration of Conformity (DoC) for additional regulatory compliance information. To obtain product certifications and the DoC for this product, visit ni.com/certification, search by model number or product line, and click the appropriate link in the Certification column.
Environmental Management
NI is committed to designing and manufacturing products in an environmentally responsible manner. NI recognizes that eliminating certain hazardous substances from our products is beneficial to the environment and to NI customers.
For additional environmental information, refer to the Minimize Our Environmental Impact web page at ni.com/environment. This page contains the environmental regulations and directives with which NI complies, as well as other environmental information not included in this document.
Waste Electrical and Electronic Equipment (WEEE)
电子信息产品污染控制管理办法(中国RoHS)
Backplane
Size | 3U-sized; one system slot (with three system expansion slots) and 17 peripheral slots. Compliant with IEEE 1101.10 mechanical packaging. PXI Express Specification compliant. Accepts both PXI Express and CompactPCI (PICMG 2.0 R 3.0) 3U modules. |
Backplane bare-board material | UL 94 V-0 Recognized |
Backplane connectors | Conforms to IEC 917 and IEC 1076-4-101, UL 94 V-0 rated |
System Synchronization Clocks
10 MHz System Reference Clock: PXI_CLK10
Maximum slot-to-slot skew | 250 ps |
Accuracy | ±25 ppm max (guaranteed over the operating temperature range) |
Maximum jitter | 5 ps RMS phase-jitter (10 Hz–1 MHz range) |
Duty-factor | 45% to 55% |
Unloaded signal swing | 3.3 V ±0.3 V |
100 MHz System Reference Clock: PXIe_CLK100 and PXIe_SYNC100
Maximum slot-to-slot skew | 100 ps |
Accuracy | ±25 ppm max (guaranteed over the operating temperature range) |
Maximum jitter | 3 ps RMS phase-jitter (10 Hz to 12 kHz range), 2 ps RMS phase-jitter (12 kHz to 20 MHz range) |
Duty-factor for PXIe_CLK100 | 45% to 55% |
Absolute differential voltage (When terminated with a 50 Ω load to 1.30 V or Thévenin equivalent) | 400 to 1000 mV |
External 10 MHz Reference Out (Timing and Synchronization Option)
Accuracy | ±25 ppm max (guaranteed over the operating temperature range) |
Maximum jitter | 5 ps RMS phase-jitter (10 Hz–1 MHz range) |
Output amplitude | 1 Vpp ±20% square-wave into 50 Ω, 2 Vpp unloaded |
Output impedance | 50 Ω ±5 Ω |
External 10 MHz Reference In (Timing and Synchronization Option)
Frequency | 10 MHz ±25 ppm |
Input amplitude | 100 mVpp to 5 Vpp square-wave or sine-wave |
Maximum jitter introduced by backplane | 1 ps RMS phase-jitter (10 Hz to 1 MHz range) |
Rear panel SMA input impedance | 50 Ω ±5 Ω |
Remote Inhibit and Chassis Monitoring Connector (Timing and Synchronization Option)
|
| |||||||||||
|
Mechanical
|
Weight | 13.5 kg (29.8 lb) |
Chassis materials | Sheet Aluminum (5052-H32, 5754-H22), Extruded Aluminum (6063-T5, 6060-T6), Plate Aluminum (6063-T5, 6061-T6), Cold Rolled Steel, Cold Rolled Stainless Steel, Sheet Copper (C110), Santoprene, Urethane Foam, PC-ABS, Nylon, Polycarbonate, Delrin, Polyethylene, Polyamide (FR-106), Neodymium Magnet |
Finish | Conductive Clear Iridite on Aluminum, Electroplated Nickel on Cold Rolled Steel, Electroplated Zinc on Cold Rolled Steel, Electroplated Nickel on Copper |
The following figures show the PXIe-1084 chassis dimensions. The holes shown are for the installation of the optional rack mount kits. You can install those kits on the front or rear of the chassis, depending on which end of the chassis you want to face toward the front of the instrument cabinet. Notice that the front and rear chassis mounting holes (size M4) are symmetrical.
In This Section
- Electrical
- Chassis Cooling
- Environmental
- Shock and Vibration
- Acoustic Emissions
- Safety
- Electromagnetic Compatibility
- CE Compliance
- Environmental Management
- Backplane
- System Synchronization Clocks
- 10 MHz System Reference Clock: PXI_CLK10
- 100 MHz System Reference Clock: PXIe_CLK100 and PXIe_SYNC100
- External 10 MHz Reference Out (Timing and Synchronization Option)
- External 10 MHz Reference In (Timing and Synchronization Option)
- Remote Inhibit and Chassis Monitoring Connector (Timing and Synchronization Option)
- 10 MHz System Reference Clock: PXI_CLK10
- Mechanical