Counter Input:Count Edges:Gate:Input:Hysteresis Property
- Updated2023-02-21
- 1 minute(s) read
Counter Input:Count Edges:Gate:Input:Hysteresis Property
Short Name: CI.CountEdges.Gate.Hyst
Property of DAQmx Channel
Specifies a hysteresis level applied to the CI.CountEdges.Gate.ThreshVoltage. When CI.CountEdges.Gate.When is High, the source signal must fall below CI.CountEdges.Gate.ThreshVoltage minus the hysteresis before the counter resumes counting. When CI.CountEdges.Gate.When is Low, the source signal must rise above CI.CountEdges.Gate.ThreshVoltage plus the hysteresis before the counter resumes counting.
Remarks
The following table lists the characteristics of this property.
Permissions | read/write |
Resettable | yes |
Settable while task is running | device-specific |
Available in Run-Time Engine | yes |