NI-DAQ™mx C Reference

Content Type
Programming Language
Current manual
Table of Contents
Product DocumentationNI-DAQ™mx C ReferenceStart >> More >> Trigger WindowCurrent page
Table of Contents

Start >> More >> Trigger Window

Start >> More >> Trigger Window

Data Type: float64
Description: Specifies the period of time in seconds after the task starts during which the device may trigger. Once the window has expired, the device stops detecting triggers, and the task will finish after the device finishes acquiring post-trigger samples for any triggers detected. If no triggers are detected during the entire period, then no data will be returned. Ensure the period of time specified covers the entire time span desired for trigger detection to avoid missed triggers. Specifying a Trigger Window of -1 causes the window to be infinite.

You can get/set/reset this property using:
  DAQmxGetStartTrigTrigWin
  DAQmxSetStartTrigTrigWin
  DAQmxResetStartTrigTrigWin