Data Record System AD Specifications

Definitions

Warranted specifications describe the performance of a model under stated operating conditions and are covered by the model warranty. Warranted specifications account for measurement uncertainties, temperature drift, and aging. Warranted specifications are ensured by design or verified during production and calibration.

Characteristics describe values that are relevant to the use of the model under stated operating conditions but are not covered by the model warranty.

  • Typical specifications describe the performance met by a majority of models.
  • Nominal specifications describe an attribute that is based on design, conformance testing, or supplemental testing.
  • Measured specifications describe the measured performance of a representative model.

Specifications are Warranted unless otherwise noted.

Conditions

Refer to ni.com/manuals for detailed specifications on the specific instruments used within the Data Record System AD (Data Record System).

Specifications are valid for the system and all included instruments under the following conditions unless otherwise noted.

  • Data Record System environmental characteristics are met
  • Instrument-level conditions are met

Physical Characteristics

Dimensions
Width

PXIe-1092DC

303.3 mm (11.94 in.)

PXIe-1095DC

445.5 mm (17.54 in.)

Depth

PXIe-1092DC and PXIe-1095DC

463.6 mm (18.25 in.)

Height

PXIe-1092DC and PXIe-1095DC

177.1 mm (6.97 in.)

Weight

Empty PXIe-1092DC with power supply installed

11.7 kg (25.7 lb)

Empty PXIe-1095DC with two power supplies installed

16.4 kg (36.2 lb)

DC Power Supply Field Wiring Specifications

Notice Use only copper wire. For use in class 1 circuits only.
Note Refer to the Data Record System AD User Manual for the power supply connection requirements.

Gauge

2.5 mm2 to 16 mm2 (14 AWG to 6 AWG) conductor

Wire strip length

12 mm (0.47 in.)

Temperature rating

60 °C minimum

Wires per terminal

1

Torque for screw terminals

1.7 N · m to 1.8 N · m (15 lb · in. to 15.9 lb · in.)

Single ferrule

Barrel length

12 mm (0.47 in.)

Maximum cross section of conductor plus ferrule

16 mm2 (6 AWG)

Recommended crimping tool

Crimpfox 16 S crimping tool

Connector securement

Securement type

Screw locking

Torque for screw flanges

0.3 N · m (2.7 lb · in.)

Protective Earthing

When using the product with hazardous voltage PXIe modules or I/O (>30 VAC, 42.4 Vpk, 60 VDC), connect the product to the protective earth terminal before connecting to DC power.

Notice The facility installation shall provide a means for connection to protective earth, and qualified personnel shall install a protective earthing conductor from the protective earthing terminal on the product to the protective earth wire in the facility.
Notice Use only copper wire to connect the protective earthing terminal of your product to the protective earth wire in the facility.

Protective Earth Terminal Wiring

Grounding wire gauge

2.1 mm2 (14 AWG)

Ring lug

# 8

Protective earth terminal torque

1.13 N · m (10 lb · in.)

Power Requirements

Power Guidelines

Notice This product is for use only with the Data Record System AD 500W DC Power Supply (NI part number 861354-01).

Power Specifications

Note Total available output power refers to the output power available for the controller and instruments in your chassis. This is the minimum specification guaranteed by design; the total available output power may be higher.

Input voltage rating (per power supply for the PXIe-1095DC)[1]1 Do not exceed the current rating of the branch circuit providing power to the chassis.

9 V at 68 A

30 V at 19 A

Operating voltage range

9 VDC to 30 VDC

PXIe-1092DC total available output power

283 W

PXIe-1095DC total available output power with dual power supplies

680 W

Maximum power consumption per PXI slot

58 W at 55 °C, 82 W at 40 °C

Over-current protection

Internal fuse in line

Main power disconnect

The installation must contain a suitable switch or circuit breaker for power disconnect. It must be suitably located and easily reached, and marked as the disconnect device for the equipment.

Required power cord(s)

2.5 mm2 to 16 mm2 (14 AWG to 6 AWG) conductor(s)

Note Select the proper conductor size based on power source and cable routing. Ensure conductor insulation and cable construction are sufficient for the application and adhere to applicable electrical codes. Ensure none of the conductor is exposed.
Table 1. DC Output
Voltage Rail PXIe-1092DC Maximum Current PXIe-1095DC Maximum Current (Dual Power Supplies) Load Regulation Maximum Ripple and Noise (20 MHz BW)
+5V_AUX 3 A 4.2 A ±5% 50 mVpp
+12 V 22.3 A 55 A ±5% 100 mVpp
+5 V 26.5 A 21.5 A ±5% 50 mVpp
+3.3 V 36 A 60 A ±5% 50 mVpp
-12 V 1.75 A 1.3 A ±5% 50 mVpp
Table 2. Backplane Slot Current Capacity
Slot +5 V V (I/O) +3.3 V +12 V -12 V 5 VAUX
System Controller Slot 15 A - 15 A 30 A - 3 A
System Timing Slot - - 9 A 6 A - 1 A
PXI Express Peripheral Slot (PXIe-1095DC only) - - 9 A 6 A - 1 A
Hybrid Peripheral Slot with PXI-5 Peripheral - - 9 A 6 A - 1 A
Hybrid Peripheral Slot with PXI-1 Peripheral 6 A 5 A 6 A 1 A 1 A -
Expansion Slot (PXIe-1092DC only) - - 9 A 6 A - 1 A
Note Total System Controller Slot current should not exceed 45 A.
Note PCI V(I/O) pins in Hybrid Peripheral Slots are connected to +5 V.
Note The maximum power dissipated in a peripheral slot should not exceed 82 W.

Over-current protection

All outputs protected from short circuit and overload with automatic recovery

Over-voltage protection

+12 V, +5 V, and +3.3 V clamped at 20% to 30% above nominal output voltage

Chassis Cooling

Module cooling

PXIe-1092DC

Forced air circulation (positive pressurization) through two 210 CFM fans

PXIe-1095DC

Forced air circulation (positive pressurization) through three 210 CFM fans

Module slot airflow direction

Bottom of module to top of module

Module intake

Rear of chassis

Module exhaust

Top of chassis

Slot cooling capacity

82 W

Secondary cooling

Forced air circulation (positive pressurization) through one 70 CFM fan

Side intake

Right side of chassis

Side exhaust

Left side of chassis

Power supply cooling

Forced air circulation through two integrated fans

Power supply intake

Rear of chassis

Power supply exhaust

Top of chassis

Timing and Synchronization upgrade intake

Right side of chassis

Timing and Synchronization upgrade exhaust

Top of chassis

Minimum chassis cooling clearances

Top and sides

44.45 mm (1.75 in.)

Back

101.60 mm (4.00 in.)

Environmental Characteristics

Temperature

Operating

0 °C to 55 °C for ≤ 58 W module operation

0 °C to 40 °C for > 58 W module operation

Storage

-40 °C to 71 °C

Humidity

Operating

10% to 90%, noncondensing

Storage

5% to 95%, noncondensing

Pollution Degree

2

Maximum altitude

2,000 m

Shock and Vibration

Operational shock

30 g peak, half-sine, 11 ms pulse (IEC-60068-2-27.)[2]2 This product meets the requirements of the environmental standards for electrical equipment for measurement, control, and laboratory use. Meets MIL-PRF-28800F Class 2 limits.

Operational random vibration

5 Hz to 500 Hz, 0.3 grms

Non-operating vibration

5 Hz to 500 Hz, 2.4 grms (IEC 60068-2-64.) Non-operating test profile exceeds the requirements of MIL-PRF-28800F, Class 3.

Acoustic Emissions

Sound Pressure Level (at Operator Position)

Tested in accordance with ISO 7779. Meets MIL-PRF-28800F requirements.

58 W/82 W Profile PXIe-1092DC PXIe-1095DC
Auto Fan (up to 30 °C ambient) 51.6 dBA 54.5 dBA
High Fan 63.7 dBA 66.1 dBA

Sound Power Level

Tested in accordance with ISO 7779.

58 W/82 W Profile PXIe-1092DC PXIe-1095DC
Auto Fan (up to 30 °C ambient) 62.8 dBA 64.8 dBA
High Fan 74.1 dBA 77.7 dBA
Note The protection provided by the Data Record System can be impaired if it is used in a manner not described in this documentation.

Backplane System Synchronization Clocks

10 MHz System Reference Clock: PXI_CLK10

Maximum slot-to-slot skew

250 ps

Accuracy

±25 ppm maximum (guaranteed over the operating temperature range)

Maximum jitter

5 ps RMS phase-jitter (10 Hz to 1 MHz range)

Duty-factor

45% to 55%

Unloaded signal swing

3.3 V ±0.3 V

Note For other specifications, the Data Record System complies with the PXI-1 Hardware Specification.

100 MHz System Reference Clock: PXIe_CLK100 and PXIe_SYNC100

Maximum slot-to-slot skew

100 ps

Accuracy

±25 ppm maximum (guaranteed over the operating temperature range)

Maximum jitter

3 ps RMS phase-jitter (10 Hz to 12 kHz range), 2 ps RMS phase-jitter (12 kHz to 20 MHz range)

Duty-factor for PXIe_CLK100

45% to 55%

Absolute differential voltage (When terminated with a 50 Ω load to 1.30 V or Thévenin equivalent)

400 mV to 1000 mV

Note For other specifications, the Data Record System complies with the PXI-5 PXI Express Hardware Specification.

External 10 MHz Reference Out (Timing and Synchronization Option, Rear Panel SMA)

Accuracy

±80 ppb maximum within 1 year of calibration adjustment within 0 °C to 55 °C operating temperature range (after 24 hours of operation); ±50 ppb/year long-term stability (after 72 hours of operation)

Maximum jitter

5 ps RMS phase-jitter (10 Hz to 1 MHz range)

Output amplitude

1 Vpp ±20% square-wave into 50 Ω, 2 Vpp unloaded

Output impedance

50 Ω ±5 Ω

External Clock Source

Frequency

10 MHz ±25 ppm

Input amplitude

External 10 MHz Reference IN (Timing and Synchronization option, rear panel SMA)

100 mVpp to 5 Vpp square-wave or sine-wave

System timing slot PXI_CLK10_IN

5 V or 3.3 V TTL signal

Maximum jitter introduced by backplane

1 ps RMS phase-jitter (10 Hz to 1 MHz range)

Rear panel SMA input impedance (Timing and Synchronization option)

50 Ω ±5 Ω

PXI Star Trigger

Maximum slot-to-slot skew

250 ps

Backplane characteristic impedance

65 Ω ±10%

For other specifications, the Data Record System complies with the PXI-1 Hardware Specification.

PXI Differential Star Triggers: PXIe-DSTARA, PXIe-DSTARB, and PXIe-DSTARC

Maximum slot-to-slot skew

150 ps

Maximum differential skew

25 ps

Backplane differential impedance

100 Ω ±10%

For other specifications, the Data Record System complies with the PXI-5 PXI Express Hardware Specification.

Remote Inhibit and Chassis Monitoring Connector (Timing and Synchronization Option)

Inhibit input signal

Input voltage range

-0.5 V minimum to 5.5 V maximum

VIH

2.0 V

VIL

0.8 V

Input impedance

High-Z (>10 kΩ typical)

Note Internal 10 kΩ pull-up to an internal +3.3V_AUX rail.
Fault output signal

Output voltage range

0 V to 3.3 V typical

VOH

2.4 V minimum (|IOH| < 8 mA)

VOL

0.4 V maximum (|IOL| < 8 mA)

Output impedance

65 Ω typical

PFI lines

Input voltage range

-0.5 V minimum to 4.6 V maximum

VIH

2.0 V

VIL

0.8 V

Input impedance

High-Z (>10 kΩ typical)

Output voltage range

0 V to 3.3 V typical

VOH

2.4 V minimum (|IOH| < 8 mA)

VOL

0.4 V maximum (|IOL| < 8 mA)

Output impedance

65 Ω typical

Hardware Components

The following components are used within the Data Record System.

Note Detailed specifications for hardware components are available online at ni.com/manuals.
Table 3. Required Hardware Components
Component Type Part Description
Chassis (select one) PXIe-1092DC 10-slot (7 hybrid slots) 3U PXI Express Chassis
PXIe-1095DC 18-slot (5 hybrid slots) 3U PXI Express Chassis
PXI Controller (select one) PXIe-8861 2.8 GHz quad-core Intel Xeon PXI controller
PXIe-8880 2.3 GHz eight-core Intel Xeon PXI controller
PXIe-8881 [3]3 The PXIe-8881 controller is functionally supported, but its high power consumption levels must be taken into account during power budgeting. 3.9 GHz eight-core Intel Xeon PXI controller
Customer-Provided Peripheral Components Keyboard and mouse USB keyboard and optical USB mouse
Monitor Computer monitor
The Data Record System includes the Timing and Synchronization chassis upgrade, but your system must contain at least one of the following instruments in order to enable this functionality:
  • PXIe-1486
  • PXIe-1487
  • PXIe-8523
  • PXIe-8522
  • PXIe-8521
  • PXIe-8510
  • PXI-6683H
Note The maximum quantities listed in the following table are based on power budgeting constraints as well as chassis slot capacity.
Table 4. Optional Hardware Components
Component Type Part Description Maximum Quantity in PXIe-1092DC Maximum Quantity in PXIe-1095DC Cable Connection Type
Camera Interface PXIe-1486 2-slot FPD-LINK III interface instrument, 8 input deserializers option or 4 input deserializers and 4 output serializers option 2 5 FPD-Link III with power over coax cable
PXIe-1487 2-slot GMSL interface instrument, 8 input deserializers option or 4 input deserializers and 4 output serializers option 2 5 GMSL2 with power over coax cable
PXIe-7976 2 GB DRAM PXI FPGA instrument for FlexRIO, K410T FPGA, 3.2 GB/s 5 12 Adapter module
PXIe-8245 1 Gigabit Ethernet instrument, 4 port 8 17 Ethernet cable
PXIe-8246 Power over Ethernet, 1 Gigabit Ethernet instrument, 4 port 8 17 Ethernet cable
Automotive Bus Interface PXIe-8523 100/1000BASE-T1 automotive Ethernet interface instrument, 4 port 5 17 Automotive Ethernet
PXIe-8522 1000BASE-T1 automotive Ethernet interface instrument, 4 port 5 17 Automotive Ethernet
PXIe-8521 100BASE-T1 automotive Ethernet interface instrument, 4 port 8 17 Automotive Ethernet
PXI-8517 FlexRay interface, 2 port 7 5 9-pin D-SUB serial connector,

SMB coax cable

PXIe-8510 CAN/LIN through NI-XNET interface (vehicle networks), 2 port or 6 port 8 17 XNET to CAN/LIN transceiver
PXIe-8240 40 Gigabit Ethernet instrument, 2 port 6 17 Ethernet cable
PXIe-8238 10 Gigabit Ethernet instrument, 2 port 8 17 Ethernet cable
PXIe-8245 1 Gigabit Ethernet instrument, 4 port 8 17 Ethernet cable
PXIe-8246 Power over Ethernet, 1 Gigabit Ethernet instrument, 4 port 8 17 Ethernet cable
PXIe-8623 100/1000BASE-T Ethernet interface instrument, 4 port, with 802.1AS timestamping 5 17 Ethernet cable
PXIe-6592R High-speed serial instrument (10 Gbps) with SFP+ adapter 3 12 Ethernet cable,

SMB coax cable

NI-9962 3-pin push-in spring terminal (4 count) for automotive Ethernet 5 17 Automotive Ethernet
Timing and Synchronization PXI-6683H TCXO (GPS, IRIG-B, IEEE 1588) 7 5 SMB coax cable,

Ethernet cable

Data Storage PXIe-8267 [4]4 Documentation for the 4 TB variant of the PXIe-8267 applies to the 15 TB variant with the exception of the storage specifications, power consumption, and slot cooling capacity requirements. Refer to PXIe-8267 Safety, Environmental, and Regulatory Information for requirements specific to the 15 TB variant. 15 TB SSD, data storage instrument (5 GB/s), 1 slot 3 12 N/A
PXIe-8394 x8 Gen 3 MXI-Express daisy chain interface 5 17 MXI-Express cable
Slot Filler PXI Filler Panel 1-slot PXI filler panel 9 17 N/A

1 Do not exceed the current rating of the branch circuit providing power to the chassis.

2 This product meets the requirements of the environmental standards for electrical equipment for measurement, control, and laboratory use.

3 The PXIe-8881 controller is functionally supported, but its high power consumption levels must be taken into account during power budgeting.

4 Documentation for the 4 TB variant of the PXIe-8267 applies to the 15 TB variant with the exception of the storage specifications, power consumption, and slot cooling capacity requirements. Refer to PXIe-8267 Safety, Environmental, and Regulatory Information for requirements specific to the 15 TB variant.